6 Alarms 11.03
6.1 Alarms for SINUMERIK 840digital
© Siemens AG 2003 All Rights Reserved
6-314 SINUMERIK 840D/SIMODRIVE 611 digital SINUMERIK Safety Integrated (FBSI) - Edition 11.03
$MA_SAFE_STOP_SWITCH_TIME_F.
– 85 Delay time, pulse cancellation, bus failure
$MN_SAFE_PULSE_DIS_TIME_BUSFAIL.
– 86 Not assigned
– 87 Not assigned
– 88 Not assigned
– 89 Encoder limit frequency $MA_SAFE_ENC_FREQ_LIMIT (only
Performance_2).
– 1000 Check timer (watchdog) has expired: If a channel is signaled an
SGE change in the other channel, then this is checked using this
check (watchdog) timer as to whether the change timer in
the other channel expires..
– 1001 (only assigned on the drive, refer to Alarm 300911)
– 1002 User agreement inconsistent: Data for the user
agreement are different in both monitoring channels after
2 sec. have expired.
%3 = status of the user agreement, NCK.
%4 = status of the user agreement, 611D.
– 1003 Reference tolerance $MA_SAFE_REFP_POS_TOL
exceeded
– 1004 Plausibility error, user agreement.
– 1005 Pulses already cancelled during test stop selection.
– 1006 (only assigned on drive, refer to Alarm 300911).
– 1007 (only assigned on drive, refer to Alarm 300911).
– 1008 (only assigned on drive, refer to Alarm 300911).
– 1009 Pulses are not cancelled after the test stop time
$MA_SAFE_PULSE_DIS_CHECK_TIME.
– 1010 Pulses are not cancelled for a test with external pulse
cancellation after the test stop time
$MA_SAFE_PULSE_DIS_CHECK_TIME.
– 1011 NCK/drive acceptance test status differs.
– 1020 Communications error between NCK and the
drive monitoring channel.
Response NC start inhibit in this channel
Alarm display
If safe monitoring was active, STOP B was also automatically triggered. It is
necessary to power-down/power-up the control (power on).
Remedy Find the difference between the monitoring channels. The fault code %2
indicates the cause of the alarm.
It is possible that the safety-relevant machine data is no longer the same (if
required, re-load), or the safety-related inputs do not have the same signal level
(measure).
If no error of this type is apparent, an error may have occurred in the CPU, e.g.
a "flipped" memory cell. This can be temporary (in this case it can be cleared
using a power on) or permanent (if it re-occurs after power on, replace the
hardware).
Error codes for STOP F for 840D/611D:
0: No error in this channel. Search for the cause in the other channel.
1: Result list 1. The functions are controlled differently via the SGEs;
evaluate the fine error coding in the 611D MDs 1391 and 1392.
2: Result list 2. Check the tolerance of the cams, evaluate the fine error
coding in the 611D-MDs 1393 and 1394.
3: Actual position. Incorrect encoder evaluation (check MDs). Different
standstill positions have been saved.
4: No crosswise data comparison.
5: Function enable signals Enter equal MDs.
6: Limit value for SG1. Enter equal MDs.
7: Limit value for SG2. Enter equal MDs.
8: Limit value for SG3. Enter equal MDs.
9: Limit value for SG4. Enter equal MDs.
10: Standstill tolerance. Enter equal MDs.