EasyManuals Logo

Siemens SIPROTEC 7SD80 User Manual

Siemens SIPROTEC 7SD80
416 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #269 background imageLoading...
Page #269 background image
Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
269
Figure 3-29 Connection of the PC via modem - basic example
Checking a Connection Using Direct Link
In case of an optical fiber link (as shown in Figure 3-27 or 3-29) or via copper conductor link, this connection is
checked as follows:
• Both devices at the link ends have to be switched on.
• Check in the event log or in the spontaneous annunciations:
– If the message „PDI FO con. to.“ (protection data interface connected with no. 3243) is provided
with the device index of the other device in case of an optical fiber conductor, a link has been established
and one device has recognized the other.
– If the message „PDI Cu con. to.“ (protection data interface connected with no. 3244) is provided
with the device index of the other device in case of a copper connection, a link has been established and
one device has recognized the other.
– The device indicates „Slave Login“, no. 3492 or „Master Login“, no. 3491 if the other device has
been detected.
• In case of an incorrect communication link, the indication „PDI FO faulty“ (no. 3230) or „PDI Cu
faulty“ (no. 3232) is displayed. In this case, check the connection again:
– Are the connections correct and not swapped?
– Are the cables free from mechanical damage, intact and the connectors locked?
– Otherwise repeat the verification.
Continue with the margin heading „Consistency of Connection and Parameterization“.
Consistency of Connection and Parameterization
Having performed the above checks, the linking of a device pair has been completely tested and connected to
auxiliary supply voltage. Now the devices contact each other on their own account.
• Check now the Event Log or in the spontaneous annunciations of the device where you are working:
– Indication no. 3243 „PDI FO con. to.“ (protection interface connected with).
– If the parameterization of the devices is consistent, i.e. the requirements have been observed when
setting the function scope (Section 2.1.1), the power system data 1 (2.1.3.1), the power system data 2
(2.1.6.1), the protection interface parameters (Section 2.1.8.2), the fault indication for the verified inter-
face also disappears, i.e. no. 3230 „PDI FO faulty“ or no. 3232 „PDI Cu faulty“. The commu-
nication and consistency check has thus been completed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD80 and is the answer not in the manual?

Siemens SIPROTEC 7SD80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD80
CategoryProtection Device
LanguageEnglish

Related product manuals