Technical Data
4.1 General Device Data
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
286
IEC 60870-5-103
redundant
RS485
Isolated interface for data transfer to a control center
Connection Back case bottom, mounting location "B",
RJ45 socket
Test voltage 500 V; 50 Hz
Transmission speed min. 2 400 Bd, max. 57 600 Bd;
factory setting 19 200 Bd
Bridgeable distance Max. 0.62 miles
Profibus RS485 (DP)
Connection Back housing bottom, mounting location "B",
9-pin D-sub socket via straight Profibus con-
nector (6KG1500-0EA02 )
Test voltage 500 V; 50 Hz
Transmission speed Up to 1.5 MBd
Bridgeable distance 1 000 m (0.62 miles) at 93.75 kBd
546.81 yd at 187.5 kBd
218.72 yd at 1.5 MBd
Profibus FO (DP)
FO connector type ST connector
Double ring
Connection Back case bottom, mounting location "B"
Transmission speed Up to 1.5 MBd
Recommended: > 500 kBd with normal casing
Optical wavelength λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
When using glass fiber 50/125 μm or glass
fiber 62.5/125 µm
Permissible optical signal at-
tenuation
max. 8 dB, with glass fiber 62.5/125 µm
Bridgeable distance Max. 0.93 miles
DNP3.0 /MODBUS RS485
Connection Back case bottom, mounting location "B", 9-
pin DSUB socket
Test voltage 500 V; 50 Hz
Transmission speed Up to 19.200 Baud
Bridgeable distance Max. 0.62 miles
DNP3.0 /MODBUS FO
FO connector type ST connector transmitter/receiver
Connection Back case bottom, rear mounting location
"B"
Transmission speed Up to 19.200 Baud
Optical wavelength λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
When using glass fiber 50/125 μm or glass
fiber 62.5/125 µm
Permissible optical signal at-
tenuation
max. 8 dB, with glass fiber 62.5/125 µm
Bridgeable distance Max. 0.93 miles