Technical Data
4.1 General Device Data
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
287
Ethernet electrical (EN 100) for
IEC61850 and DIGSI
Connection Back case bottom, mounting location "B",
2 x RJ45 socket
100BaseT in acc. with IEEE802.3
Test voltage (with regard to the
socket)
500 V; 50 Hz
Transmission speed 100 Mbit/s
Bridgeable distance 21.87 yd
Ethernet electrical (EN 100) for
IEC61850 and DIGSI
Connection Back case bottom, mounting location "B",
LC connector 100BaseF in acc. with
IEEE802.3
Transmission speed 100 Mbit/s
Optical wavelength 1300 nm
Bridgeable distance Max. 1.24 miles