Appendix
A.9 Information List
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
372
- Setting Group C is active (P-
GrpC act)
Change Group IntSP On
Off
* * LED BO 192 25 1 Yes
- Setting Group D is active (P-
GrpD act)
Change Group IntSP On
Off
* * LED BO 192 26 1 Yes
- Fault Recording Start (FltRecSta) Osc. Fault Rec. IntSP On
Off
*mLEDBO
- Reset Minimum and Maximum
counter (ResMinMax)
Min/Max meter IntSP
_Ev
ON *
- CB1-TEST trip/close Phases
ABC (CB1tst ABC)
Testing - *
- Controlmode REMOTE (ModeR-
EMOTE)
Cntrl Authority IntSP On
Off
* LED BO
- Control Authority (Cntrl Auth) Cntrl Authority IntSP On
Off
* LED BO 101 85 1 Yes
- Controlmode LOCAL (ModeLO-
CAL)
Cntrl Authority IntSP On
Off
* LED BO 101 86 1 Yes
- 52 Breaker (52Breaker) Control Device CF_D
12
On
Off
* BO 240 160 20
- 52 Breaker (52Breaker) Control Device DP On
Off
* BI CB 240 160 1 Yes
- Disconnect Switch (Disc.Swit.) Control Device CF_D
2
On
Off
* BO 240 161 20
- Disconnect Switch (Disc.Swit.) Control Device DP On
Off
* BI CB 240 161 1 Yes
- Ground Switch (GndSwit.) Control Device CF_D
2
On
Off
* BO 240 164 20
- Ground Switch (GndSwit.) Control Device DP On
Off
* BI CB 240 164 1 Yes
- Interlocking: 52 Open (52 Open) Control Device IntSP * * *
- Interlocking: 52 Close (52 Close) Control Device IntSP * * *
- Interlocking: Disconnect switch
Open (Disc.Open)
Control Device IntSP * * *
- Interlocking: Disconnect switch
Close (Disc.Close)
Control Device IntSP * * *
- Interlocking: Ground switch Open
(GndSw Open)
Control Device IntSP * * *
- Interlocking: Ground switch Close
(GndSw Cl.)
Control Device IntSP * * *
- Q2 Open/Close (Q2 Op/Cl) Control Device CF_D
2
On
Off
* BO 240 162 20
- Q2 Open/Close (Q2 Op/Cl) Control Device DP On
Off
* BI CB 240 162 1 Yes
- Q9 Open/Close (Q9 Op/Cl) Control Device CF_D
2
On
Off
* BO 240 163 20
- Q9 Open/Close (Q9 Op/Cl) Control Device DP On
Off
* BI CB 240 163 1 Yes
- Fan ON/OFF (Fan ON/OFF) Control Device CF_D
2
On
Off
* BO 240 175 20
- Fan ON/OFF (Fan ON/OFF) Control Device DP On
Off
* BI CB 240 175 1 Yes
- >Cabinet door open (>Door
open)
Process Data SP On
Off
**LEDBIBOCB10111Yes
- >CB waiting for Spring charged
(>CB wait)
Process Data SP On
Off
**LEDBIBOCB10121Yes
- >Error Motor Voltage (>Err Mot V) Process Data SP On
Off
* * LED BI BO CB 240 181 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation