EN 110 A6V10816676_----_d Siemens Building Technologies
Status displays
Display Description
The data displayed apply for:
Heat
Cool = Cold
Imp1 = Impulse input 1
Imp2 = Impulse input 2
(empty) = Displayed value is the current value
M (Memory) = Value on a monthly or due date
Displayed value is a date value:
Day = Current date
M-Day = Date applies for a saved annual or monthly value
Displayed value is a checksum:
Check = Checksum refers to the current consumption value
M-Check = Checksum is valid for a saved annual or monthly value
Currentoavailable
No energy counting -> no temperature difference
Currentoavailable
Energy counting
IrDA communication is currently active
Operating state display
Display Description Measures/notes
Communication credit
of the module interface
or IrDA exceeded
Is eliminated after the credit period
(module = current day; IrDA = current
month) has passed
Operating time
expired
Device must be replaced
Flow direction in-
correct
Check installation
(note arrow on ometeringelement)
Check piping
Check recirculating pumps and
thermostats for correct function
Temperature sensors
have been mixed up or
ttedincorrectl
Check whether ometeringelement
hasbeenttedintherightstrandor
check type of installation of tempera-
ture sensor