2. Press the <ALARM ACK> key under the flashing red LED. The following items should occur:
a. The tone-alert is silenced and the display will show pertinent report information, such as shown below.
I
FIRST FLOOR EAST WING ROOM 31
PULL STATION
ALARM
I
b. The SYSTEM ALARM LED changes from flashing to steady ON, and all alarm conditions are
acknowledged.
c. Pressing the <ALARM ACK> key scrolls through all alarms in chronological order.
HOW TO SILENCE THE ALARM SIGNALS
Press the <ALARM SILENCE> key and read the display. The alphanumeric display will show signal status.
ALARM SILENCE IN PROGRESS...
HOW TO RESET THE SYSTEM
When the alarm condition has been cleared, restore or replace all affected devices (pull stations, smoke dletectors
etc.) in accordance with the instructions provided with each device.
Press the <SYSTEM RESET> key. After a delay, if the initiating device is restored, the system will return to normal
and the alphanumeric display should show the following message.
I
SYSTEM IS NORMAL
8:23:55
MON 7 3EC 92
I
iNDlVlDUAL ACKNOWLEDGE PANEL OPERATION DURING ALARM CONDITIONS
An
INDIVIDUAL ACKNOWLEDGE
of a System Alarm Condition is accomplished in the following manner.
1. Unlock and open the enclosure door. The alphanumeric display on the interface panel reports the number
of alarm conditions, as shown below.
I
***ALARM***
Press <ACK> to review.
ALARMS = 1
SUPERVISORY = 0
TROUBLE = 0
I
10