7.  Press  the  <Fl>  key  (above  the  display)  to  choose  the  “Clear  All”  option. 
8.  When  finished,  press  the  &LR>  key  on  the  ENTRY  keypad  to  escape  from  the  Main  Menu. 
VIEWING ABNORMAL  SYSTEM CONDITIONS WITH THE DISPLAY  TIME KEY 
NOTE: 
The  system  must  have  an abnormal  condition  showing  on the  alphanumeric  display  before  the  Display  Time 
Key  can  be  used. 
To view  Abnormal  System  Conditions  with  the  Display  Time  Key,  perform  the  following  procedure. 
1.  Press  the  appropriate  acknowledge  (ACK)  key  on  the  operator  interface  panel  to  view  the  desirecl  point. 
2.  Press  and  hold  the  <DISPLAY  TIME>  key  on  the  DISPLAY/ACTION  keypad  to  display  the  time  and  date 
tag  for  the  first  event. 
NOTE: 
If the  log  was  cleared  while  the  event  condition  existed,  the  time  and  date  tag  will  not  be ,found. 
3.  Alternately,  press  the  appropriate  acknowledge  key and  <DISPLAY  TIME>  key  to scroll  through  events  and 
display  their  time  and  date  tags. 
CLEARING  THE ALARM  VERIFICATION  TALLY 
To clear  an  Alarm  Verification  Tally,  perform  the  following  procedure. 
NOTE: 
The  following  procedure  is for  a MAPNET  II@ device.  To  clear  an Alarm  Verification  Tally  on a ZONIEi, press 
the  <NET->  key,  enter  the  Node  number,  and  press  the  <ENTER>  key.  Then,  press  the  <ZN  l>  key  and 
enter  the  zone  number.  Press  the  <ENTER>  key.  Then,  go  to  Step  5 and  continue  the  procedure. 
1.  Press  the  <NET  ->  key,  enter  the  Node  number,  and  press  the  <ENTER>  key. 
2.  Press  the  <MAP  6>  key  on the  ENTRY  keypad. 
l 
The  display  now  prompts  you  for  the  MAPNET  II@ channel  and  device  number. 
3.  Using  the  ENTRY  keypad,  press  the  appropriate  numeric  key  for  the  device’s  channel  (1 through  9,  or  0), 
the  hyphen  C-> key,  and  the  appropriate  numeric  key(s)  for  the  device  number  (1 through  127).  Then,  press 
the  <ENTER>  key. 
4.  To  verify  the  Node  number  and  MAPNET  II@device  number,  press  the  <FUNCTION>  key  on the  DISPLAY/ 
ACTION  keypad. 
5.  To  display  the  Alarm  Verification  Tally,  press  the  <FUNCTION>  key  and  the  <NEXT>  or cPREVIOLlS>  key 
until  the  display  shows  “Fl  =Clear  Verification  Tally”. 
6.  Press  the  cFl>  key  to clear  the Alarm  Verification  Tally.  If your  Access  Level  is insufficient  for this  operation, 
a statement  to  that  effect  will  appear  on  the  display,  and  no  action  will  occur. 
7.  To  exit  from  this  operation,  press  the  cCLR>  key  on the  ENTRY  keypad  until  the  original  display  reappears. 
82