7. Press the <Fl> key (above the display) to choose the “Clear All” option.
8. When finished, press the &LR> key on the ENTRY keypad to escape from the Main Menu.
VIEWING ABNORMAL SYSTEM CONDITIONS WITH THE DISPLAY TIME KEY
NOTE:
The system must have an abnormal condition showing on the alphanumeric display before the Display Time
Key can be used.
To view Abnormal System Conditions with the Display Time Key, perform the following procedure.
1. Press the appropriate acknowledge (ACK) key on the operator interface panel to view the desirecl point.
2. Press and hold the <DISPLAY TIME> key on the DISPLAY/ACTION keypad to display the time and date
tag for the first event.
NOTE:
If the log was cleared while the event condition existed, the time and date tag will not be ,found.
3. Alternately, press the appropriate acknowledge key and <DISPLAY TIME> key to scroll through events and
display their time and date tags.
CLEARING THE ALARM VERIFICATION TALLY
To clear an Alarm Verification Tally, perform the following procedure.
NOTE:
The following procedure is for a MAPNET II@ device. To clear an Alarm Verification Tally on a ZONIEi, press
the <NET-> key, enter the Node number, and press the <ENTER> key. Then, press the <ZN l> key and
enter the zone number. Press the <ENTER> key. Then, go to Step 5 and continue the procedure.
1. Press the <NET -> key, enter the Node number, and press the <ENTER> key.
2. Press the <MAP 6> key on the ENTRY keypad.
l
The display now prompts you for the MAPNET II@ channel and device number.
3. Using the ENTRY keypad, press the appropriate numeric key for the device’s channel (1 through 9, or 0),
the hyphen C-> key, and the appropriate numeric key(s) for the device number (1 through 127). Then, press
the <ENTER> key.
4. To verify the Node number and MAPNET II@device number, press the <FUNCTION> key on the DISPLAY/
ACTION keypad.
5. To display the Alarm Verification Tally, press the <FUNCTION> key and the <NEXT> or cPREVIOLlS> key
until the display shows “Fl =Clear Verification Tally”.
6. Press the cFl> key to clear the Alarm Verification Tally. If your Access Level is insufficient for this operation,
a statement to that effect will appear on the display, and no action will occur.
7. To exit from this operation, press the cCLR> key on the ENTRY keypad until the original display reappears.