If the  <ALARM  ACK>  key  is passcode  protected,  you  cannot  use  this  key  to  acknowledge  alarms  unless  you  have 
the  required  access  level.  See  Operator  Access  Levels  (Section  9)  and  Log  In Procedure  (Section  1). 
There  are  two  types  of  acknowledges  for  the  NDU:  Global  Acknowledge  and  Individual  Acknowledge.  Each 
acknowledge  type  operates  with  the  System  Alarm  Condition  in the  following  manner. 
l  Global  Acknowledge  - 
When  Global  Acknowledge  is  used,  a  single  key  press  of  the  <ALARM  ACK>  key 
acknowledges  all alarm  status  changes  in the  system.  If status  change  information  is required,  you  may  review 
this  data  (after  a 60  second  delay)  by  pressing  the  <ALARM  ACK>  key  and  reading  the  total  numbl2r  of  alarm 
status  changes  on  the  alphanumeric  display. 
l  Individual  Acknowledge 
(For  NFPA  72-1990  Requirements)  -  If  an  alarm  condition  n’as  been 
acknowledged  with  the  <ALARM  ACK>  key  and  further  unacknowledged  conditions  remain  in the  system,  the 
tone-alert  continues  to sound  and  the  next  status  change  is shown  on  the  alphanumeric  display.  This  process 
repeats  until  all  changes  are  acknowledged.  When  this  occurs,  the  tone-alert  is  silenced,  and  the  highest 
priority  acknowledge  change  is  indicated  pn  the  display. 
ALARM  SILENCE  KEY 
CAUTION 
THE  ALARM  SILENCE  KEY  PRESS WILL  CAUSE  FIRE ALARM  EVACUATION  SIGNALS  TO TURN 
--- 
QFJ.  FOLLOW  LOCAL  PROCEDURES TO SILENCE ALARM  EVACUATION SIGNALS. 
When  an  alarm  condition  exists,  various  signals,,  auxiliary  relays,  the  city  connection,  and  the  tone-a.lert  may 
activate,  depending  on  the  system  configuration  and  the stage  of the  alarm  condition.  The  <ALARM  SILEFJCE>  key, 
when  pressed,  turns  OFF  all  circuits  programmed  to  follow  the  Alarm  Silence  key.  The  <ALARM  SILENCE>  key 
press  will: 
l 
Turn  OFF  signal  circuits 
l 
Display  a  message,  such  as  the  one  shown  below. 
ALARM  SILENCE  IN  PROGRESS... 
Alarm  Silence  Software  Considerations 
The  following  software  functions  affect  ALARM  SILENCE  operation. 
l 
If a 
Coded  Input  Device 
is  activated,  the  <ALARM  SILENCE>  key  press  may  be  ignored  until  this  function 
has  completed  coding.  Notification  appliances  cannot  be silenced  when  a coded  station  iS in alarm,  however, 
the  flashing  LED  will  change  from  flashing  ON  to  steady  ON  when  the  <ALARM  ACK>  key  is  pushed.  The 
notification  appliances  will  be  silenced  automatically  when  coding  is complete. 
l 
If the 
Alarm  Silence  Inhibit  Function 
is activated  but  not  completed,  the  <ALARM  SILENCE>  ke!y press  is 
ignored.  The  message,  “ALARM  SILENCE  INHIBITED”,  is displayed  for  a short  time  to  indicate  the  action  was 
not  taken.  The  message  “ALARM  SILENCE/SYSTEM  RESET  ALLOWED  INHIBIT  TIMER  COMPLETE”  is 
displayed  when  the  inhibit  function  times  out.  If selected,  the  alarm  silence  inhibit  may  be  programmed  from  1 
to  99  minutes.  When  selected,  signals  cannot  be  silenced  (and  the  system  cannot  be  reset)  until  the 
programmed  time  has  elapsed. 
l 
If 
Waterflow/Sprinkler  Devices 
are  activated,  notification  appliances  may  or may  not  be silenced  (depending 
on  local  code  requirements).  Usually,  a dedicated  bell  will  continue  to  sound  to  indicate  water  flow. 
l 
Some  visual  notification  appliances  may  continue  to flash  until  the  system  is reset. 
l 
Speaker  circuits  remain  ON  until  the  system  is reset,  but  the  audio  tone/message  is silenced. 
12