-93-
No.EX※※-OMX1011
The [Module Properties] screen is displayed, to perform setup.
(1) Name: Enter the required unit name.
(2) Select the data format of Comm: Connection Parameters.
(3) IP Address: Enter the IP address setting for the SI unit.
(4) Assembly Instance: Perform setting as shown below.
Description
Decimal
Common Format
"Data-INT"
"Data-SINT"
Input
100
100
Output
150
150
Configuration
105
105
(5) Size: Perform setting as shown below.
Description
Decimal
Common Format
"Data-INT"
"Data-SINT"
Input
MIN. 1 word
MAX.110 words
MIN. 2 byte
MAX.220 byte
Output
MIN. 1 word
MAX.110 words
MIN. 2 byte
MAX.220 byte
Configuration
When configuration assembly fundtion is not used: Set to "0".
When using the configuration assembly fanuction:
According to unit part number and unit quantity, it needs to calcurate
the total cinfiguration data size. If the total data size is not set
correctly, EtherNet/IP communication can not be established.
: Select the setting depending on the existence of diagnostic data and the unit type connected.
(4)
(2)
(3)
(1)
(5)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600-SEN3 and is the answer not in the manual?

SMC Networks EX600-SEN3 Specifications

General IconGeneral
BrandSMC Networks
ModelEX600-SEN3
CategoryI/O Systems
LanguageEnglish

Related product manuals