-47-
No.EX※※-OMX1011
Troubleshooting
•Troubleshooting
When any failure happens with this Fieldbus system, the following chart is used to identify the cause of the
failure.
Error status is reflected from the parameter setting of the Fieldbus system.
When a failure occurs, take the appropriate countermeasures referring to the LED display, the troubleshooting
and the parameter setting.
If a cause applicable to the failure cannot be identified, it indicates that the Fieldbus system itself is broken.
The Fieldbus system breakage can be caused by the operating environment. Contact SMC separately to
obtain countermeasures.
Yes
No
If the error is not eliminated even after
supplying power, the unit failure is possible.
Replace the applicable I/O unit.