Hazardous situations for the user and for the Prime 600 system
Hazard Before making any change to the power or
measurement connections, make sure that the system is not
injecting.
Hazard Following a high current injection, the hoses and
connections may be very hot and may cause burns.
Hazard Do not manually open a circuit through which current
passes as this may generate high voltages.
Hazard Never connect the power supply hoses to the line
before connecting them to the equipment.
When performing tests, make sure that the circuit is grounded.
If it is a switch, we recommend grounding both sides.
Hazard The Prime 600 system is not designed to perform
tests on highly inductive loads.
Hazard Never work with the system if you observe severe
damage or damp on it.