Version 5.2 Sourcefire 3D System Installation Guide 184
Hardware Specifications
Sourcefire 8000 Series Devices
Chapter 6
Power supply Dual 750 W redundant power supplies designed for AC or DC.
AC Voltage: 100 VAC to 240 VAC nominal (85 VAC to 264 VAC
maximum)
AC Current: 10A maximum over the full range, per supply
5A maximum for 187 VAC to 264 VAC, per supply
AC Frequency range: 47 Hz to 63 Hz
DC Voltage: -48 VDC nominal referenced to RTN
-40 VDC to -72 VDC maximum
DC Current: 20A maximum, per supply
Operating temperature 10°C to 35°C (50°F to 95°F)
Non-operating temperature
-20
o
C to 70
o
C (-29
o
F to 158
o
F)
Operating humidity 5% to 85% non-condensing
Non-operating humidity 5% to 90%, non-condensing with a maximum wet bulb of 28°C at
temperatures from 25°C to 35°C (77°F to 95°F)
Altitude 0 ft (sea level) to 6000 ft (0 to 1800 m)
Cooling requirements up to 2225 BTU/hour
You must provide sufficient cooling to maintain the appliance within its
required operating temperature range. Failure to do this may cause a
malfunction or damage to the appliance.
Acoustic noise Max normal operating noise is 81.6 dB LWAd (High temp.)
Typical normal operating noise is 81.4 dB LWAd.
Operating shock No errors with half a sine wave shock of 2G (with 11 msec. duration)
Airflow
Front to back, 210 ft
3
(6 m
3
) per minute
Restriction of the airflow such as blocking the front or back or
enclosing the unit in a cabinet without sufficient clearance may cause
the unit to overheat, even if the ambient temperature is in the
operating range.
Airflow through the appliance enters at the front and exits at the rear.
The minimum recommended clearance in the front and back is 7.9”
(20cm). This minimum can only be used if you can ensure a supply of
low temperature air at the front of the appliance.
82xx Family Physical and Environmental Parameters (Continued)