35 © STULZ GmbH – all rights reserved EN/06.2019/G57
C7000 INSTRUCTIONS fOR A/C UNITS
Default setting:
Baudrate: 9600
Databits: 8
Parity: 0
Stopbit: 2
Protocol: Modbus Master
Default setting:
Baudrate: 9600
Databits: 8
Parity: 0
Stopbit: 1
Protocol: SCP (WIB)
Configuration of the interfaces RS4852 and RS4853
The parameters of the RS4852 (BMS bus) and RS4853
(component bus) interfaces can be configured.
This is necessary, if Modbus components must be control-
led by RS4853, which only can be configured by Modbus
and which does not work with fixed settings (9600 8n2
for RS4853).
Baudrate (9600, 19200)
Bit per word (8)
Parity setting (0=none, 1=odd, 2=even)
Stopbit setting (1, 2)
Protocol setting (16=Modbus Master)
Application of new parameter setting
1
Commands:
Component bus:
Baudrate (9600, 19200)
Bit per word (8)
Parity setting (0=none, 1=odd, 2=even)
Stopbit setting (1, 2)
Protocol setting (0, 1, 2)
2
Application of new parameter setting
1
Commands:
BMS bus:
Explanation of indexed parameters:
1 - The change of parameters becomes effective only by
this command. This allows you to change several parame-
ters at the same time.
2 - 0 = no protocol
1 = SCP (WIB)
2 = Modbus Slave
16 = Modbus Master
ioc 01:>serbus 3
RS485 bus 3
Baud..........:19200
Databits......:8
Parity........:0
Stopbit.......:2
Protocol......:16
serbus 3 baud 19200
serbus 3 databits 8
serbus 3 parity 0
serbus 3 stopbit 2
serbus 3 protocol 16
serbus 3 init 1
ioc 01:>serbus 2
RS485 bus 2
Baud..........:9600
Databits......:8
Parity........:0
Stopbit.......:1
Protocol......:1
serbus 2 baud 9600
serbus 2 databits 8
serbus 2 parity 0
serbus 2 stopbit 1
serbus 2 protocol 1
serbus 2 init 1