196
loaddefault dx1
DX1 DX2 CW CW2 AGCW1 AGCW2 GE11 GE12
Compressor 1 configured
1 1 - - 1 1 1 1
Compressor 2 configured
- 1 - - - 1 - 1
Sensor 5 configured
- - - - 1 1 1 1
Sensor 6 configured
- - - - - - 1 1
Sensor 7 configured
- - - - - - 1 1
Sensor 8 configured
- - - - - - - 1
GE/CW valve configured
- - 1 1 1 1 1 1
G valve configured
- - - - - - 1 1
Dehumidification reduction
- - 20% 20% 20% 20% 20% 20%
Input D GE/CW valve
- - - 3 - - - -
Cooling priority
- - - - 1 1 - -
Unit type A/G GE ACW/GCW CW
1 circuit
dx1 ge11 agcw1 cw
2 circuits
dx2 ge12 agcw2 cw2
EN/06.2019/G57  © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS fOR a/C UNITS
11.1 Preconfigurations
Several default configurations for different unit cooling systems are
stored in the C7000IOC.
C7000 command: The table contains the parameters for the
C7000IOC command.
The following table displays the differences in relation to the default settings when a pre-configuration
is selected.
Notes:
- For all unit versions except CW and CW2 of the series CyberAir 2/3 the electronic expansion valve
must be configured.