16 EN/06.2019/G57 © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS FOR A/C UNITS
4. Info menus
4.1 Info commands - C7000
Each component- or A/C unit command which is entered without parameters only displays information
without changing adjustments. However, the following commands give a general overview about the unit state
and configuration.
equip - shows the components and its number, also the extension cards (dig/ana)
state - shows the unit- and functional (cooling, heating etc.) runtimes and the unit/component state
is 1 - - setpoints, actual zone/unit values, limit values
is 2 - - alarm delay, priority, common alarm assignment for each limit value alarm
is 3 - - control type, sensor limitation values, cooling priority, winter operation, ups mode, outside temp.
for
condensation pressure reduction, gradient for press. reduction, winter start delay, bus/global
address,
temperature difference for overload activation, last service, service interval,
- assignment of in/outputs: common alarm, winter operation, remote on/off, ups operation,
actual temp./humidity, CW cooling off
wprg - shows the programmed timer function for the week (week program)
events - shows all registered events (maximum 200, alarms & unit on/off)
event 1 Prints the last events from number 1 to 20
event 2 Prints the last events from number 21 to 40
:
event 10 Prints the last events from number 181 to 200
event 20.07.2007 Prints all events of this date
event comp Prints all events which contain the expression „comp“
event clear Erases the event memory
event 1 13 Prints the events from number 1 to 13
ups - shows the ups (uninterrupted power supply) configuration
water - shows all settings concerning the water alarm.
fire - shows all settings concerning the fire alarm.
phase - shows all settings concerning the phase alarm.
flow - shows all settings concerning the water flow alarm.
service - shows all settings concerning the service alarm.
ain - shows the assignment of the analog inputs.
aout - shows the assignment of the analog outputs.
din - shows the assignment of the digital inputs.
dout - shows the assignment of the digital outputs.
option - Shows all information about activated special software options
e.g.: 002. Restart after fire (active)
option all
Shows all possible special software options
001. OTE
002. Restart after fire
003. automatic alarm reset after limit value excess
004. SATS
When the fire alarm has ended the controller switches to
the state, in which it has been before the alarm occured e.g.
sequencing stop.