11. Default configurations
Unit parameters Range Value
Unit name
16 characters Unit name
Bus address
0 - 19 0
Global address
0 - 32767 1
Local stop
0 - 1 1
Monitoring stop
0 - 1 0
Sequencing stop
0 - 1 0
Terminal language 0 : English
1 : German
0
Temperature unit
0: °C 1: °F 0
Temperature setpoint
5 - 50°C 24°C
Temperature setpoint, night
5 - 50°C 27°C
Setpoint, relative humidity
5 - 90 % r. h. 45% r. h.
Setpoint, specific humidity
0.0 - 20.0 g/kg 8.5 g/kg
Water pressure setpoint
0 - 6 bar 1.5 bar
Supply air pressure setpoint
0 - 327.67 Pa 0.00 Pa
Condensation pressure DX 1/2
0 - 40 bar 18/18 bar
Condensation pressure Mix 1/2
0 - 40 bar 12/12 bar
SAPSM delay
0 - 65535 s 0 s
Winter start delay
0 - 300 s 180 s
Summer/winter change-over
5 - 35°C 16°C
Summer/winter hysteresis
1 - 9,9 K 2 K
Cooling priority
0: GE 1: CW 2: DX 0
Additional capacity - Cooling
0 - 9.9 K 0.0 K
Additional capacity - Humidification
0 - 20% r.h. 0% r.h.
Additional capacity - Dehumidification
0 - 20% r.h. 0% r.h.
Integral factor
0 - 10% 0%
Output D common alarm
0 - 31 6
Output D winter operation
0 - 31 0
Input D remote on/off
0 - 43 0
Output D local stop
0 - 31 0
Input D CW stop
0 - 43 0
Type of control
01. Mai 1
Limiting control - start temperature
0 - 40°C 16°C
Limiting control - start temperature 2
0 - 40°C 0°C
Limiting control - temp. gradient
0 - 20 K 0.5 K
Minimum temperature
0 - 40°C 0°C
Maximum temperature
0 - 40°C 40°C
Limiting control - humidity start
0 - 90 % r.h. 70% r.h.
Limiting control - humidity gradient
0 - 20% r.h. 0.5% r.h.