C7000 INSTRUCTIONS fOR A/C UNITS
The parameter "zone" is not a zone parameter but can be
adjusted separately for each unit.
Due to his context it is displayed in this table.
Unit parameters Range Value
Unit runtime 0 - 2.147.483.647* 0 h
Stop time 0 - 2.147.483.647 0 h
Cooling runtime 0 - 2.147.483.647 0 h
Heating runtime 0 - 2.147.483.647 0 h
Humidification runtime 0 - 2.147.483.647 0 h
Dehumidification runtime 0 - 2.147.483.647 0 h
Free cooling runtime 0 - 2.147.483.647 0 h
Mixed operation runtime 0 - 2.147.483.647 0 h
Last service - day 1 - 31 1
Last service - month 1 - 12 8
Last service - year 0 - 50 4
Service interval 0 - 24 0
Alarm priority service alarm 0 - 31 0
Common alarm for service alarm 0 - 1 0
UPS - input D 0 - 43 0
UPS - fan admitted 0 - 1 1
UPS - cooling admitted 0 - 1 1
UPS - heating admitted 0 - 1 100%
UPS - humidification admitted 0 - 1 1
UPS - dehumidification admitted 0 - 1 1
Zone parameters Range Value
Zone 0 - 20 0
Sequencing time 0 - 65535 0 h
Test sequencing 0 - 1 0
Valid alarms 1 - 27 113, 2427
Number of defective units 0 - 20 0
Emergency temperature 0 - 40 16°C
Zone fan speed nMax 0 - 100 85%
CW standby management 0 - 1 0
Standby state 0 - 1 0
Zone parameters Range Value
T/H average value determination 0 - 1 1
Pressure average value determ. 0 - 1 1
T/H Average value delay 0 - 255 s 120 s
Average val. determ. w. standby units 0 - 1 0
GE start temperature, air -100 - 100°C 18°C
GE rel. start temperature, air 0 - 9,9 K 0 K
GE hysteresis, air 0 - 9,9 K 0 K
GE start temperature, water -100 - 100°C 10°C
GE rel. start temperature, water 0 - 9,9 K 0 K
GE hysteresis, water 0 - 9,9 K 0 K
Fan speed nMax (SAPSM) 0 - 100 % 0 %
Supply air pressure value 0 - 3 1