184 EN/06.2019/G57 © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS fOR a/C UNITS
The values in brackets display the range.
*(-327.68 - +327.67)
Alarms Range Fire Water Flow Phase Bus alarm Addr. conflict
Alarm input D 0 - 43 0 0 0 0 - -
Alarm priority 0 - 31 0 0 0 0 0 0
Common alarm 0 - 1 1 1 1 1 0 0
Alarm delay 0 - 100 s 5 s 5 s 5 s 5 s 5 s -
Restart 0 - 1 0
Room temperature Supply air temperature Water temperature 1 / 2
min max min max min max
Value 5°C (050) 35°C (555) 5°C (050) 35°C (555) -20°C (-2030) 45°C (1050)
Alarm delay 30 s (065535) 30 s (065535) 30 s (065535) 30 s (065535) 30 s (065535) 30 s (065535)
Alarm priority 0 (031) 0 (031) 0 (031) 0 (031) 0 (031) 0 (031)
Common alarm 1 1 1 1 1 1
Room humidity Supply air humidity Supply air pressure
min max min max min max
Value 5%h.r (090) 90%h.r (5200) 5%h.r (090) 90%h.r (5200) 0.00 Pa (*) 100.00 Pa (*)
Alarm delay 30 s (065535) 30 s (065535) 30 s (065535) 30 s (065535) 30 s (065535) 30 s (065535)
Alarm priority 0 (031) 0 (031) 0 (031) 0 (031) 0 (031) 0 (031)
Common alarm 1 1 1 1 1 1
General alarms
Limit alarms
Hour Range 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
monday 0 - 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
tuesday 0 - 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ... ...
sunday 0 - 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Week programm
Range External alarm 1 External alarm 2 ... External alarm 10
Component configured
0 - 1 0 0 ... 0
Input D 0 - 43 0 0 ... 0
Alarm priority 0 - 31 0 0 ... 0
Common alarm 0 - 1 0 0 ... 0
Alarm delay 0 - 250 s 5 s 5 s ... 5 s
Alarm text 20 characters Externer_Alarm_in_01 Externer_Alarm_in_02 ... Externer_Alarm_in_10
External alarms