185 © STULZ GmbH – all rights reserved EN/06.2019/G57
C7000 INSTRUCTIONS fOR A/C UNITS
High pressure alarm Range Circuit 1 Circuit 2
Alarm input D 0 - 43 0 0
Alarm priority 0 - 31 0 0
Common alarm 0 - 1 1 1
Alarm delay 0 - 100 s 5 s 5 s
Low pressure alarm Range Circuit 1 Circuit 2
Alarm input D 0 - 43 0 0
Alarm priority 0 - 31 0 0
Common alarm 0 - 1 1 1
Alarm delay 0 - 100 s 5 s 5 s
Range Compressor 1 Compressor 2
Component configured 0 - 1 0 0
Compressor type 1 - 2 1 1
Summer start temperature 0 - 9,9 K 0,4 K 0,6 K
Summer hysteresis 0 - 9,0 K 0,7 K 0,7 K
Winter start temperature 0 - 9,9 K 0,7 K 0,9 K
Winter hysteresis 0 - 9,0 K 0,7 K 0,7 K
Quick start 0 - 1 0 0
Start delay by FC 0 - 600 s 0 s 0 s
ASTP threshold 0 - 10,0 bar 0,0 bar 0,0 bar
ASTP hysteresis 0 - 10,0 bar 0,0 bar 0,0 bar
Output D 0 - 31 2 7
Start disable, input D 0 - 31 0 0
LP management time 0 - 100 h 0 h 0 h
LP management pressure 0 - 10 bar 5 bar 5 bar
LP management restart 0 - 10 0 0
HP management time 0 - 100 0 h 0 h
HP management pressure 0 - 35 bar 21 bar 21 bar
HP management restart 0 - 10 0 0
HP management mode 0 - 1 0 0
Pause 10 - 1000 s 180 s 180 s
Minimum runtime 0 - 1000 s 180 s 180 s
Runtime 0 - 2.147.483.647 h 0 h 0 h
Components
Compressor