186 EN/06.2019/G57 © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS fOR a/C UNITS
ICC - Integrated cooling circuit
Range ICC
Component configured 0 - 1 0
Global address 1 - 247 1
Start temperature 0,0 - 9,9 0,4
Hysteresis 0,0 - 9,9 0,8
Min runitme after start 0 - 1000 s 240 s
Min runitme after dehumidification 0 - 1000 s 240 s
P factor 0 - 100 10
I factor 0 - 100 40
D factor 0 - 100 0
Minimum power 17,0 - 40,0 % 17,0 %
Maximum power 50,0 - 100,0 % 100,0 %
Minimum pressure (threshold) 0 - 40,0 bar 0 bar
EEV value 0 - 100,0 % 0 %
EEV time 0 - 60 s 0 s
Alarm priority reachability 0 - 31 0
Common alarm reachability 0 - 1 0
Alarm priority ICC 0 - 31 0
Common alarm ICC 0 - 1 0
Alarm priority LP 0 - 31 0
Common alarm LP 0 - 1 0
Runtime 0 - 2.147.483.647 h 0 h