The corresponding commands:
Components/Sensor/121
After the selection of the sensor you can enter the alarm delay for the limit
alarm
and for the sensor failure alarm in seconds.
With the offset you can calibrate the sensor with the help of a reference mea-
suring instrument.
Compare the PHYSICAL VALUE with the value of the reference measuring
instrument and modify the parameter "Offset" until the displayed value "Phys.
val." corresponds to the value read on the reference instrument.
If, instead of a temperature, the
expression "reset" is entered, the
sensor calibration is deleted.
Insert here the value of the reference
measuring instrument.
5.4 Components
5.4.1 Sensor
sensor 1 alarmdelay 7
sensor 1 alarmdelaybr 8
sensor 1 trim 22.3
Operate