195 © STULZ GmbH – all rights reserved EN/06.2019/G57
C7000 INSTRUCTIONS fOR A/C UNITS
Electric meter
Calculation of cooling capacity (EER)
ACT control
ECOCool louverECOCool Control
Data logger
Range Electric meter
Modbus address 1 - 247 1
Component configured 0 - 1 0
Range EER
Heat capacity 1 - 10000 4187
Density 0 - 10 1.000
Range ACT
Control mode 1 - 4 1
Time 1 - 255 s 120
Range ECOCool
Output A 0 - 20 0
Start temperature -9.9 - 9.9 K 0.1 K
Gradient 0.1 - 9.9 K 0.6 K
Range ECOCool
Function configured 0 - 1 0
Start outside temperature –100 - +100°C 18°C
Hysteresis 0 - 9,9 K 0 K
Difference start 0 - 9,9 K 3 K
Emergency hysteresis 0 - 9,9 K 3 K
Anti freeze –50 - +50 °C 5 °C
Delay 0 - 255 Min. 10 Min.
Outside moisture min. 0 - 25.5 g/kg 0.0 g/kg
Outside moisture hyst. 0 - 9.9 g/kg 0.0 g/kg
Data logger 1 Data logger 2
Data number 0 (0 - 1440) 0 (0 - 1440)
Interval 0 min (0 - 60000) 0 min (0 - 60000)
Type 1 (1 - 19) 1 (1 - 19)