40
EN/06.2019/G57  © STULZ GmbH – all rights reserved
C7000 INSTRUCTIONS fOR A/C UNITS
The corresponding commands:
Values
Air/Humidity
The controller offers the possibility to start a standby unit when an adjustable
negative humidity difference to the setpoint of the relative humidity is achieved.
This difference can be adjusted by the parameter "Overloadstart"
. The
adjustment 0.0% disables this function.
In the same way you can make start a standby unit when an adjustable positive
humi dity difference to the setpoint of the relative humidity is achieved. This dif-
ference can be adjusted by the parameter "Overloadstart dehumidific."
.
When the humidity difference is obtained the A/C unit, so far as it is defined as
standby unit, will be started. The sequencing function is not influenced by this.
The parameter "corr. low limit" is only relevant for CyberSonic units.
Concerning the limit alarms "Room humidity too low
/too high " and Supply
air humidity too low
/too high " you can adjust:
a. common alarm release (1=yes).
b. alarm priority
All combinations are possible.
load humi 10.5
load dehumi 5.5
minhumi room
maxhumi room commonalarm 1
minhumi supply alarmprio 8
maxhumi supply
a
b
Values/Air/Humidity
Operate