C7000 INSTRUCTIONS fOR A/C UNITS
The corresponding commands:
With a condensation pressure sensor (either part of G-valve or separate option)
high pressure alarms can be equally managed for the same reasons as LP
alarms.
You can limit the number of allowed compressor restarts in "RESTARTS"
within a time space you can adjust in the left column of the sixth line. You can
define the time space in the right column of the same line
b.
If the threshold
a of the HP within this time space is excessed at least the
adjusted number of times, the measure which you have adjusted in "mode"
is
taken.
off - 0: A high pressure alarm is triggered and the compressors of this refriger-
ant circuit are stopped. A compressor restart is possible after the reset
of the alarm.
on - 1: The high pressure management is listed in the event-log and the com-
pressors of this refrigerant circuit are stopped. After the compressor
pause has elapsed, the compressors can be started again.
For A/C units with more than one compressor per refrigerant circuit the follow-
ing is valid:
Compressor 1, 3 and 5 are assigned to the first refrigerant circuit, compressor
2, 4 and 6 to the second refrigerant circuit.
The parameters, which concern the LP- and HP management of compressor 1
are also valid for compressor 3 and 5 and automatically change after the set-
ting of compressor 1 in the menu of compressor 3 and 5 also.
Such an interconnection also exists between compressor 2, 4 and 6.
NOTICE
An LP or HP management is possible for on/off-compressors only.
comp 1 wac cpmaxtries 3
comp 1 wac cpmax 21
comp 1 wac cpmaxint 2
comp 1 wac hpmode 1