C7000 INSTRUCTIONS fOR a/C UNITS
The corresponding commands:
Components
Cooling/Conden. fan
If condensers with proportionally controlled fans are used for the condensation
of the refrigerant, these can be controlled by the C7000 using a PID control.
By setting the parameter "ACTIVE" on 1 in the first line you add a condenser fan
to the configuration
➊.
By the digital output
➋, which you can set in the second line, the enabling signal
for the condenser fan is output.
In the third line you can determine the analog output
➌.
As for any alarm the following parameters can be determined.
Alarm parameters: In the Operate menu:
➍ Digital input ➐ Alarm delay
➎ Common alarm release
➏ Alarm priority
Config/....
Operate/....
cond 1 conf 1
cond 1 dout 8
cond 1 aout 2
cond 1 alarm 13
cond 1 commonalarm 1
cond 1 alarmprio 19
cond 1 alarmdelay 5