6-5              
 
Communication 
Address 
Parameter  Name & Function  Default Unit
Setting 
Range 
Control 
Mode 
RS232 RS485
PI/P control switch mode. 
Setting Explanation 
0 
Switch from PI to P if the torque command 
is larger than Cn016. 
1 
Switch from PI to P if the speed command 
is larger than Cn017. 
2 
Switch from PI to P if the acceleration rate 
is larger than Cn018. 
3 
Switch from PI to P if the position error is 
larger than Cn019. 
Cn015.0 
 
4 
Switch from PI to P be the input contact 
PCNT. 
Set one of the multi function terminals to 
option 03.  
4 X 
0 
│ 
4 
Automatic gain 1& 2 switch 
Setting Explanation 
0 
Switch from gain 1 to 2 if torque command 
is greater than Cn021. 
1 
Switch from gain 1 to 2 if speed command 
is greater than Cn022. 
2 
Switch from gain 1 to 2 if acceleration
command is greater than Cn023. 
3 
Switch from gain 1 to 2 if position error
value is greater than Cn024. 
Cn015.1 
 
4 
Switch from gain 1 to 2 by input contact 
G-SEL. Set one of the multi function 
terminals to option 15. 
4 X 
0 
│ 
4 
Pi 
Pe 
S 
C07H 000FH
Automatic gain proportion switch 
Setting Explanation 
0  JSDEP new automatic gain proportion 
Cn015.3 
 
1  JSDEP old automatic gain proportion 
0 X 
0 
│ 
1 
ALL C07H 000FH
PI/P control mode switch by Torque Command
Cn016 
Set the Cn015.0=0 first. 
If Torque Command is less than Cn016  PI control is 
selected. 
If Torque Command is greater than Cn016 P control 
is selected. 
200 %
0 
│ 
399 
Pi 
Pe 
S 
C4BH 0010H
PI/P control mode switch by Speed Command 
Cn017 
Set the Cn015.0=1 first. 
If Speed Command is less than Cn017 PI control is 
selected. 
If Speed Command is greater than Cn017 P control 
is selected. 
0 rpm
0 
│ 
4500 
Pi 
Pe 
S 
C4CH 0011H
PI/P control mode switch by accelerate 
Command 
Cn018 
Set the Cn015.0=2 first. 
If Acceleration is less than  Cn018   PI control is 
selected. 
If Acceleration is greater than Cn018 P control is 
selected.  
0 rps/s
0 
│ 
18750 
Pi 
Pe 
S 
C4DH 0012H
PI/P control mode switch by position error 
number 
Cn019 
Set the Cn015.0=3 first. 
If Position error value is less than Cn019 PI control 
is selected. 
If Position error value is greater than Cn019 P 
control is selected. 
0 pulse
0 
│ 
50000 
Pi 
Pe 
S 
C4EH 0013H