6-10
Communication
Address
Parameter Name & Function Default Unit
Setting
Range
Control
Mode
RS232 RS485
Drive warning setting
Cn054
Parameter Cn054 set by hex code, and each bit
represents for each alarm. Setting the
corresponding bit to 1 for the alarm is a warn
mode. Drive warns and then triggers alarm after
continuously executing the setting time of Cn055
when alarm occurs.
Ex: Set Cn054 to 0801H, and then set Cn055 to
100 when low voltage or overspeed alarm is a
warn, which triggers alarm one second later.
0000100000000001 is the setting status,
presenting in binary.
0000 x
0000
│
FFFF
ALL C8DH 0036H
Drive warning delays the time of triggering
alarm
Cn055
Parameter Cn054 set by hex code, and each bit
represents for each alarm. Setting the
corresponding bit to 1 for the alarm is an warn
mode. Drive warns and then triggers alarm after
continuously executing the setting time of Cn055
when alarm occurs.
Ex: Set Cn054 to 0801H, and then set Cn055 to
100 when low voltage or overspeed alarm is a
warn, which triggers alarm one second later.
0000100000000001 is the setting status,
presenting in binary.
0
x10
msec
0
│
300
ALL C8EH 0037H