EasyManua.ls Logo

Thales 421 - Check Alarm Limits and Alarm Delays

Thales 421
256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LLZ 421
Operation and Maintenance Alignment Procedure LLZ−2F (LPD)
ILS 420
8−19Ed. 07.08
SOAC
8.4.5 Check Alarm Limits and Alarm Delays
NOTE: If upper limit is equal to lower limit, executive monitoring is not available.
8.4.5.1 Executive Alarm Limits
a) Open dialog ’Monitor 1 − Executive Alarm Limits’ and open dialog ’Monitor 2 − Executive Alarm
Limits’ (for MCS: dialogs ’Monitor 1/2 − Limits: Current Executive Data’).
b) Check that RF level alarm limits for all monitors are set to: 90 % (lower limit) and 110 % (upper limit).
c) Check that SDM alarm limits for all monitors are set to: 38 % (lower limit) and 42 % (upper limit).
d) Check that POS DDM alarm limits for all monitors are set to:
–0.9 % (lower limit) and +0.9 % (upper limit)
NOTE: Used for CAT III only, CAT I and CAT II require other values, see section 8.8.
e) Check that CRS WIDTH DDM alarm limits for all monitors are set to:
–2.6 % (lower limit) and +2.6 % (upper limit) of actual measured value;
example for 15.5 %: 18.1 % (upper limit) and 12.9 % (lower limit)
f) Check that CLR WIDTH DDM alarm limits for all monitors are set to:
−4 % (lower limit) and +4 % (upper limit) of the actual measured value.
g) Check that Ident AM alarm limits for all monitors are set to:
−2 % (lower limit) and +2 % (upper limit) of the actual measured value.
h) Check that Alarm delay time is set to: CAT I: 10 s; CAT II: 5 s; CAT III: 2 s (prefer. 1 s); NF: 20 s.
8.4.5.2 Far Field Alarm Limits
a) Open dialog ’Monitor 1 − Far Field Alarm Limits’ and dialog ’Monitor 2 − Far Field Alarm Limits’
(for MCS: dialogs ’Monitor 1/2 − Limits: Current Far Field Data’).
b) Check that RF level alarm limits for all monitors are set to: 71 % (lower limit) and 129 % (upper limit)
c) Check that SDM alarm limits for all monitors are set to: 38 % (lower limit) and 42 % (upper limit).
d) Check that POS DDM alarm limits for all monitors are set to:
–0.9 % (lower limit) and +0.9 % (upper limit)
NOTE: Used for CAT III only, CAT I and CAT II require other values, see section 8.8. The alarm limits
are only available if an integrated FFM is installed.
8.4.5.3 Standby Alarm Limits
a) Open dialog ’Monitor 1 − Standby Alarm Limits’ and dialog ’Monitor 2 − Standby Alarm Limits’
(for MCS: dialogs ’Monitor 1/2 − Limits: Current Standby Data’).
b) Check that RF level alarm limits for all monitors are set to: 90 % (lower limit) and 110 % (upper limit)
c) Check that SDM alarm limits for all monitors are set to: 38 % (lower limit) and 42 % (upper limit).
d) Check that POS DDM alarm limits for all monitors are set to:
–0.9 % (lower limit) and +0.9 % (upper limit)
NOTE: Used for CAT III only, CAT I and CAT II require other values, see section 8.8.
e) Check that CRS WIDTH DDM alarm limits for all monitors are set to:
–2.6 % (lower limit) and +2.6 % (upper limit) of actual measured value;
example for 15.5 %: 18.1 % (upper limit) and 12.9 % (lower limit)
f) Check that CLR WIDTH DDM alarm limits for all monitors are set to:
−4 % (lower limit) and +4 % (upper limit) of the actual measured value.
REMARK: Check pre−alarm limits. If need be adjust to 80 % of alarm limit value (recommended).

Table of Contents