IO Extender Modules 119
Chapter 3 System Description
IO Bus Cables
An IO bus cable is required for each channel and is terminated at each end by a
male 9-pin D connector suitable for rugged industrial applications. Various cable
lengths are available.
If the IO bus length is greater than 6 meters (20 feet), the bus should be terminated.
The maximum IO bus length is 200 meters (650 feet) and includes:
Length of all baseplates
•IO Extender Modules
•IO bus extension cables
Note For distances greater than 200 meters (650 feet) or for applications
requiring isolation, fiber-optic transceivers are commercially available. For
compatible units and supported distances, contact your regional customer center.

Table of Contents