226 General Considerations
Trident Planning and Installation Guide
General Considerations
The following general considerations should be observed when installing the
Trident system:
Maintain an ambient air temperature of 60°C (140°F) or less at the bottom
of each baseplate.
Separate all 440 V AC (or higher) electrical supply lines as far away from
the components as possible.
Separate AC and data wiring as much as possible.
Use best industry practices when installing wiring. For more information,
see IEEE Standard 518-1977.
Do not run cables parallel if they carry different types of signals (data versus
power); instead, cross the cables at right angles.
Maintain shield continuity and verify that shield leads are not broken.
Route cables around, rather than through, high noise areas.
Route shielded data cable along grounded surfaces such as metal cabinet
walls and in conduit or trays. Single-shielded cable is most effective when
routed along grounded surfaces.
Allow the minimum amount of unshielded wire that will accommodate the
connection.