D301087 0308 - BL20 CANopen 4-151
I/O-Module Objects
4
Object 6425
hex
- Analog Input Interrupt Lower Limit Integer
The object 6425
hex
defines the value for a lower limit.
Values below this "lower limit" can be defined as the condition for
generating an interrupt signal.
→ "6421
hex
Analog input interrupt trigger selection", page 4-145.
Table 92:
Objects 6425
hex
Feature Description/ Value
Name Analog input interrupt lower limit
Integer
Object code ARRAY
PDO-mapping No
Sub-index 00
hex
Data Type Unsigned8
Access ro
Default value, BL20 No
Sub-index 01
hex
to 8E
hex
Data Type Integer32
Access rw
Default value, BL20 00000000
hex
Note
The appropriate numerical values and number ranges for each input
variable (current, voltage, temperature...) can be found in the Ap-
pendix of the manual for BL20 I/O-modules (D300529).