Object 3064hex - XBI Param Dword
The object XBI Param Dword reads the first Param-Dword (Byte
0...3) of a module on the BL20module bus. The sub-index 1 to 74
corresponds to the module number of the BL20 module.
Byte Design. Status
Comment
Byte 7,8 PKZ
ERR
Sx
Overcurrent protective circuit-breaker, slave x
Info field for the individual indication of the tripping
a motor-protective circuit-breaker (PKZ) as error
message. If the PKZ
INFO
A is set for single diagnos-
tics, this bit field indicates the error as soon as the
PKZ of the slave Sx has tripped.
0 OK The PKZ of the slave has not tripped
or diag-nostics function has been
deactivated via the parameter setting.
1 tripped The PKZ of the slave has tripped.
Table 181:
Object 3064
hex
Feature Description
Name XBI Param Dword
Object code ARRAY
PDO-mapping No
Data type Unsigned32
Access rw
Default value No