Configuration and Programming
February 2011 3-20 P/N 06-237041-001
Figure 3-20. FenwalNET 8000-ML Set Menu Functions (Cont’d - Fig. 4 of 14)
FOOTNOTES (Figure 3-20):
12 Alarmline. Change the Configuration of an Addressable AlarmLine Module.
Purpose: To change one or more of the following Addressable AlarmLine Module (AAM) operating
characteristics for a single module or range of modules: pre-alarm and alarm thresholds as defined
by the module’s variable-threshold-setting switch; pre-alarm reporting; alarm or overheat reporting
Note: The AAM will create an “Overheat” message on the display if its alarm threshold is exceeded
and it is configured for overheat reporting. The control unit buzzer will also activate.
13 Remote Release. Configure a Remote Release.
Purpose: To change one or more of the following Remote Release Module (RRM) operating
characteristics for a single or range of modules: solenoid and initiator.
3. SET
3. SLC Devices
Cont’d
*
2. Configuration
4. Alarmline
Set AAM Configuration
Switch Setting 1 to 16 *__
Set AAM Configuration
Pre-Alarm 1: ON 2: OFF *
Set AAM Configuration
Alarm 1: Normal 2: Overheat *
5. Remote Release
Set RRM Configuration
1: Solenoid 2: Initiator *
Set AAM Configuration
SLC Devices From*__ to __
(1-255)
Set RRM Configuration
SLC Devices From*__ to __
(1-255)
*= Level-2 (Installer) Password required .
12
13
SLC Module Selection
Enter SLC Module Number (1-8):_*
SLC Module Selection
Enter SLC Module Number (1-8):_*