Configuration and Programming
P/N 06-237041-001 3-29 February 2011
Note: Wait for each SLC device to report a "Not-Registered" trouble message and ensure that all
these trouble messages have been acknowledged before selecting “AutoSetup”.
28 Assign Alarm Verification. Activate Alarm Verification for Smoke Detectors.
Purpose: To activate and de-activate alarm-verification for one or more smoke detectors. Refer to
Section 4-10.3.6.
29 Positive ALM SEQ. Activate Positive-Alarm Sequence for Smoke Detectors.
Purpose: To activate and de-activate positive-alarm sequence for one or more smoke detectors. See
Section 4-10.3.5.1 for the description of positive-alarm sequence.
30 Clear Events. Clear the System Event Log.
Purpose: To remove all previously recorded system events from the FenwalNET 8000-ML event log.
31 Clear SLC Tests. Clear the Contents of the SLC-Initiating Devices Test Log.
Purpose: To remove the most-recently recorded results of initiating devices tests from the SLC Test
Log. All initiating devices are tested once per day to confirm that they can transmit an acceptable
event-detection signal. The results of the most-recently-transmitted event signal are recorded in the
SLC Test Log.
32 Clear Walk Tests. Clear the Contents of the Walk-Test Log.
Purpose: To remove the most-recently recorded results of initiating-devices walk tests from the Walk-
Test Log. The results of the most-recently-conducted walk tests are recorded in the Walk-Test Log.
33 Resynch. Network.
Purpose: To restore uniformity of event display among the members of a networked FenwalNET
8000-ML system.