Configuration and Programming
February 2011 3-30 P/N 06-237041-001
Figure 3-25. FenwalNET 8000-ML Set Menu Functions (Cont’d - Fig. 9 of 14)
FOOTNOTES (Figure 3-25):
34 Global Acknowledge. Activate Global Acknowledge. Purpose: To enable the "Acknowledge"
Switch to process any combination of up to 30 unacknowledged supervisory or trouble events.
35 Global Acknowledge of Alarms. Configure the Global Alarm Acknowledge. Purpose: When
this feature is enabled, when the operator presses the “Acknowledge” key, all current alarms are
acknowledged. If this feature is disabled, the operator must acknowledge each alarm individually.
3. SET
5. Globals
1. Global Acknowledge
Cont’d
*
Global Acknowledge of Trouble/Supv
1: Enable 2: Disable _
*=
Level-2 (Installer) Password required .
2. Global Alarm Ack
Global Acknowledge of Alarms
1: Enable 2: Disable _
3. Alarm Verify
Assign Alarm Verification
Verification Period *___ (0 or 030-180 Seconds)
4. PAS
Assign Positive Alarm Sequence
Investigation Period___ (000-180 sec)
Assign Positive Alarm Sequence
Timer Updated
5. Nightly Test Time
Set Nightly SLC Test Time (02:00)
Nightly Test Time *__:__

(24 Hour Clock)
34
35
36
37
38

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security FenwalNET 8000-ML and is the answer not in the manual?

UTC Fire and Security FenwalNET 8000-ML Specifications

General IconGeneral
BrandUTC Fire and Security
ModelFenwalNET 8000-ML
CategoryControl Unit
LanguageEnglish