Configuration and Programming
February 2011 3-30 P/N 06-237041-001
Figure 3-25. FenwalNET 8000-ML Set Menu Functions (Cont’d - Fig. 9 of 14)
FOOTNOTES (Figure 3-25):
34 Global Acknowledge. Activate Global Acknowledge. Purpose: To enable the "Acknowledge"
Switch to process any combination of up to 30 unacknowledged supervisory or trouble events.
35 Global Acknowledge of Alarms. Configure the Global Alarm Acknowledge. Purpose: When
this feature is enabled, when the operator presses the “Acknowledge” key, all current alarms are
acknowledged. If this feature is disabled, the operator must acknowledge each alarm individually.
3. SET
5. Globals
1. Global Acknowledge
Cont’d
*
Global Acknowledge of Trouble/Supv
1: Enable 2: Disable _
*=
Level-2 (Installer) Password required .
2. Global Alarm Ack
Global Acknowledge of Alarms
1: Enable 2: Disable _
3. Alarm Verify
Assign Alarm Verification
Verification Period *___ (0 or 030-180 Seconds)
4. PAS
Assign Positive Alarm Sequence
Investigation Period___ (000-180 sec)
Assign Positive Alarm Sequence
Timer Updated
5. Nightly Test Time
Set Nightly SLC Test Time (02:00)
Nightly Test Time *__:__
(24 Hour Clock)