Configuration and Programming
February 2011 3-42 P/N 06-237041-001
FOOTNOTES (Figure 3-33):
6 On Board Circuit. Activate Control-Unit-Based Outputs.
Purpose: To manually activate control-unit outputs during system testing to confirm proper
operation.
6 On Board Circuit. De-Activate Control-Unit-Based Outputs.
Purpose: To manually de-activate control-unit outputs that were activated during system testing.
CAUTION
There is no indication at the control unit that an output is activated. Be sure to de-activate
the output after proper operation has been confirmed.
Ensure that the outputs will not activate suppression systems or critical facility
operations such as computer power. Physically disconnect all agent-release and pre-
action-sprinkler circuits and bypass all affected power-off circuits before activating any
outputs if the outputs are activating suppression systems or are shutting off power.
Restore the system to normal operating condition at the conclusion of all output
activation and any other functional tests.
CAUTION
There is no indication at the control unit that an output is activated. Be sure to de-activate
the output after proper operation has been confirmed.
Ensure that the outputs will not activate suppression systems or critical facility
operations such as computer power. Physically disconnect all agent-release and pre-
action-sprinkler circuits and bypass all affected power-off circuits before activating any
outputs if the outputs are activating suppression systems or are shutting off power.
Restore the system to normal operating condition at the conclusion of all output
activation and any other functional tests.