vacon • 101 Parameters
6
6.1.14.2 Group 3.13.2: Setpoints
Table 92. Setpoints settings
Code Parameter Min Max Unit Default ID Description
P3.13.2.1 Keypad SP 1 Varies Varies Varies 0 167
P3.13.2.2 Keypad SP 2 Varies Varies Varies 0 168
P3.13.2.3 Ramp Time 0.00 300.0 s 0.00 1068
Defines the rising and falling
ramp times for setpoint
changes. (Time to change
from minimum to maximum)
P3.13.2.4 SP Boost Activat. Varies Varies
DigIN
Slot0.1
1046
FALSE = No boost
TRUE = Boost
P3.13.2.5 Setpoint Selection Varies Varies
DigIN
Slot0.1
1047
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.13.2.6 SP 1 Source 0 22 1 332
0 = Not used
1 = Keypad setpoint 1
2 = Keypad setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature input 1
18 = Temperature input 2
19 = Temperature input 3
20 = Temperature input 4
21 = Temperature input 5
22 = Temperature input 6
AI’s and ProcessDataIn are
handled as percent (0.00-
100.00%) and scaled accord-
ing to Setpoint minimum and
maximum. NOTE: Process-
DataIn signals use 2 deci-
mals.
P3.13.2.5 SP 1 Minimum -200.00 200.00 % 0.00 1069
Minimum value at analogue
signal minimum.
P3.13.2.6 SP 1 Maximum -200.00 200.00 % 100.00 1070
Maximum value at analogue
signal maximum.
P3.13.2.10 SP 1 Boost -2.0 2.0 x 1.0 1071
The setpoint can be boosted
with a digital input.
P3.13.2.11 SP 2 Source 0 22 2 431 See par. P3.13.2.6
P3.13.2.12 SP 2 Minimum -200.00 200.00 % 0.00 1073
Minimum value at analogue
signal minimum.
P3.13.2.13 SP 2 Maximum -200.00 200.00 % 100.00 1074
Maximum value at analogue
signal maximum.
P3.13.2.17 SP 2 Boost -2.0 2.0 x 1.0 1078 See P3.13.2.10.