Parameters vacon • 102
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.14.3 Group 3.13.3: Feedbacks
Table 93. Feedback settings
Code Parameter Min Max Unit Default ID Description
P3.13.3.1 Function 1 9 1 333
1=Only Source1 in use
2=SQRT(Source1);(Flow=Con
stant x SQRT(Pressure))
3= SQRT(Source1- Source 2)
4= SQRT(Source 1) + SQRT
(Source 2)
5= Source 1 + Source 2
6= Source 1 - Source 2
7=MIN (Source 1, Source 2)
8=MAX (Source 1, Source 2)
9=MEAN (Source 1, Source 2)
P3.13.3.2 Gain -1000.0 1000.0 % 100.0 1058
Used e.g. with selection 2 in
Feedback function
P3.13.3.3 FB 1 Source 0 20 2 334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
15 = Temperature input 1
16 = Temperature input 2
17 = Temperature input 3
18 = Temperature input 4
19 = Temperature input 5
20 = Temperature input 6
AI’s and ProcessDataIn are
handled as % (0.00-100.00%)
and scaled according to
Feedback min and max.
NOTE: ProcessDataIn use
two decimals.
P3.13.3.4 FB 1 Minimum -200.00 200.00 % 0.00 336
Minimum value at analogue
signal minimum.
P3.13.3.5 FB 1 Maximum -200.00 200.00 % 100.00 337
Maximum value at analogue
signal maximum.
P3.13.3.6 FB 2 Source 0 20 0 335 See P3.13.3.3
P3.13.3.7 FB 2 Minimum -200.00 200.00 % 0.00 338
Minimum value at analogue
signal minimum.
P3.13.3.8 FB 2 Maximum -200.00 200.00 % 100.00 339
Maximum value at analogue
signal maximum.