EasyManua.ls Logo

Vacon 100X series - Page 14

Vacon 100X series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
vacon • 11 Startup
P1.22 I/O A Ref sel 1 9 5 117
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P1.23 Keypad Ref sel 1 9 2 121
Selection of ref source when
control place is keypad:
See P1.22
P1.24 Fieldbus Ref sel 1 9 3 122
Selection of ref source when
control place is Fieldbus:
See P1.22
P1.25 AI1 signal range 0 1 0 379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P1.26 AI2 signal range 0 1 1 390
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
Table 1. Quick setup parameter group

Table of Contents

Related product manuals