vacon • 11 Startup
P1.22 I/O A Ref sel 1 9 5 117
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P1.23 Keypad Ref sel 1 9 2 121
Selection of ref source when
control place is keypad:
See P1.22
P1.24 Fieldbus Ref sel 1 9 3 122
Selection of ref source when
control place is Fieldbus:
See P1.22
P1.25 AI1 signal range 0 1 0 379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P1.26 AI2 signal range 0 1 1 390
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
Table 1. Quick setup parameter group