EasyManua.ls Logo

Vacon 100X series - Page 15

Vacon 100X series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Startup vacon • 12
Service support: find your nearest Vacon service center at www.vacon.com
3
P1.27 RO1 function 0 51 2
1100
1
Function selection for Basic
R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator active
10 = Start signal active
11 = Keypad control active
12 = I/O B control activated
13 = Limit supervision 1
14 = Limit supervision 2
15 = No fucntion
16 = No fucntion
17 = Preset speed active
18 = No fucntion
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID supervision limits
22 = Ext. PID superv. limits
23 = Input press. alarm/fault
24 = Frost prot. alarm/fault
25 - 30 = No fucntion
31 = RTC time chnl 1 control
32 = RTC time chnl 2 control
33 = RTC time chnl 3 control
34 = FB ControlWord B13
35 = FB ControlWord B14
36 = FB ControlWord B15
37 = FB ProcessData1.B0
38 = FB ProcessData1.B1
39 = FB ProcessData1.B2
40 = Maintenance alarm
41 = Maintenance fault
42 = No fucntion
43 = No fucntion
44 = Block Out.1
45 = Block Out.2
46 = Block Out.3
47 = Block Out.4
48 = Block Out.5
49 = Block Out.6
50 = Block Out.7
51 = Block Out.8
52 = Block Out.9
53 = Block Out.10
54 = No function
55 = No function
56 = Auto-cleaning
active
57 = Motor Switch
Open
58 = TEST (Always
Closed)
59 = No function
Table 1. Quick setup parameter group

Table of Contents

Related product manuals