EasyManua.ls Logo

Vacon 100X series - Page 32

Vacon 100X series
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
vacon • 29 User Interfaces
Copying parameters
NOTE: This feature is available in graphical keypad only.
The parameter copy function can be used to copy parameters from one drive to another.
The parameters are first saved to the keypad, then the keypad is detached and connected to
another drive. Finally the parameters are downloaded to the new drive restoring them from the
keypad.
Before any parameters can successfully be copied from the keypad to the drive, the drive has
to be stopped before the parameters are uploaded.
First go into
User settings menu and locate the Parameter backup submenu. In the
Parameter backup submenu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made at the
factory.
•By selecting
Save to keypad you can copy all parameters to the keypad.
Restore from keypad will copy all parameters from keypad to a drive.
Figure 8. Parameter copy
NOTE: If the keypad is changed between drives of different sizes, the copied values of these pa-
rameters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phii (P3.1.1.5)
Switching frequency (P3.1.2.3)
Motor current limit (P3.1.3.1)
Stall current limit (P3.9.3.2)
Stall time limit (P3.9.3.3)
Stall frequency (P3.9.3.4)
Maximum frequency (P3.3.1.2)
STOP READY Keypad
Main Menu
Favourites
( 0 )
( 4 )
ID: M6
User settings
I/O and Hardware
( 8 )
STOP READY Keypad
Drive name
( 3 )
ID:
User settings
Application selection
HVAC
M6.5M6.5
Parameter backup
Drive
STOP READY Keypad
Restore from keypad
ID:
Restore factory defaults
M6.5M6.5.1
Save to keypad
Parameter backup
OK OK
9164.emf

Table of Contents