vacon • 91 Parameters
6
6.1.10.5 Group 3.9.6: Temperature input fault 1
NOTE! This parameter group is visible only with an option board for temperature measure-
ment (OPT-BH) installed.
Table 76. Temperature input fault 1 settings
Code Parameter Min Max Unit Default ID Description
P3.9.6.1 Temperature signal 1 0 63 0 739
Selection of signals to use for
alarm and fault triggering.
B0 = Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
B5 = Temperature Signal 6
Max value is taken of the
chosen signals and used for
alarm/fault triggering.
NOTE! Only 6 first tempera-
ture inputs are supported
(counting boards from slot A
to slot E).
P3.9.6.2 Alarm limit 1 -30.0 200.0 °C 120.0 741
Temperature limit for trig-
ging alarm.
NOTE! Only
inputs chosen with parame-
ter P3.9.6.1 are compared.
P3.9.6.3 Fault limit 1 -30.0 200.0 °C 120.0 742
Temperature limit for trig-
ging alarm.
NOTE! Only
inputs chosen with parame-
ter P3.9.6.1 are compared.
P3.9.6.4 Fault limit response 1 0 3 2 740
0 = No response
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)