Confo rm ity and standards
This product conforms to the following European directives and UK Regulations:
2014/35/EU
Directive of the council for adapting the legal regulations of member states on electrical equipment for use within specific
voltage limits.
Electrical Equipment (Safety) Regulations: 2016
Regulations implemented according to EU Directive (2014/35/EU) on electrical equipment designed for use within specific
voltage limits approved on the GB market.
2014/30/EU
Directive of the council for adapting the legal regulations of member states on electromagnetic compatibility.
Electromagnetic Compatibility Regulations: 2016
Regulations concerning the aspects on electromagnetic compatibility approved on the GB market.
Conformity is established through compliance with the following standards:
• IEC/EN/BS 62040-1:2008+A1:2013
• IEC/EN/BS 62040-2:2018
Additional information regarding adherence to these directives and regulations is included in the appendices NSR and EMC
to the Declarations of Conformity. If needed, the Declarations of Conformity can be requested to Vertiv.
2011/65/EU
Directive of the council for adapting the legal regulations of member states on the restriction of the use of certain hazardous
substances that can be used in the manufacture of electrical and electronic equipment.
The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012.
The restriction of the use of certain hazardous substances that can be used in the manufacture of electrical and electronic
equipment approved on the GB market.
W A RN IN G! High earth leakage current: E arth connection is critical before connecting the
input su p p ly (including both m ains supply and battery).
This equipm ent is installed w ith an EM C filter.
Earth leakage current is less than 3000 mA .
Tran sient and steady state earth leakag e currents, w hich m ay occur w hen the equipm ent is
started , shou ld be taken into account in the selection of instantaneous R C C Bs or R C D devices.
RC C B w h ich is sensitive to unidirectional DC pulse (class A) and insensitive to transient state
current pulse m u st be selected.
N ote also that the earth leakage currents of th e load w ill be carried b y the R CC Bs or R C D s.
The equipm ent m ust be earthed in accordance w ith th e local electrical code of practice.
1 Important Safety Instructions
2
Vertiv™ Liebert® EXM2 UPS User Manual