EasyManua.ls Logo

Vertiv Liebert EXM2 - Clearance; Cable Access Mode

Vertiv Liebert EXM2
204 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3. Vertical hanging of cabinet is not allowed.
Ensure that the weight of the UPS does not exceed the capacity of the lifting equipment. For the UPS weight, refer to Table
12.3 on page184.
The UPS cabinet can be moved by forklift or other similar lifting equipment.
For short distance movement, the castors can be used.
3.7.3 Clearance
Because the UPS has no grille at the two sides, there is no special clearance requirement on the two sides. Besides the local
regulations, to enable routine tightening of the power terminals within the UPS, it is recommended that clearance around the
front of the UPS should be enough to enable free passage of personnel with the door fully open. Meanwhile, maintain at the
back of the cabinet a clearance at least 500mm to permit adequate circulation of air coming out of the UPS.
3.7.4 Cable Access Mode
For further description, refer to Power Cable Connection Steps .
3 Mechanical Installation
31
Vertiv™ Liebert® EXM2 UPS User Manual

Table of Contents

Related product manuals