Figure 9.17 Term inals connection
N o. Description
1 PE
2 Out A
3 Out B
4 Out C
5 Out D
9.2.20 C2 Electromagnetic Shielding Option
The C2 electromagnetic shielding option enables the UPS to meet the EMC requirements of Class C2 devices. If used in
residential areas, installation restrictions or additional measures may be required to suppress RF harassment.
9.2.21 CPSS Model Option
CPSS model is optional. The UPS meets EN 50171 standards.
After the CPSS model option is configured, the output has derating requirements. The correspondence is as follows:
100 kVA CPSS (80 kVA)
120 kVA CPSS (96 kVA)
160 kVA CPSS (128 kVA)
200 kVA CPSS (160 kVA)
250 kVA CPSS (200 kVA)
9 Options
172
Vertiv™ Liebert® EXM2 UPS User Manual