12.8 Efficiency and Loss
Item Unit
Ra ted po wer (kV A)
100 120 16 0 20 0 250
Rated normal mode (full load) kW 4 4.8 6.4 8 10
Rated normal mode (No load) kW 0.4 0.6 0.6 0.8 1
ECO mode (full load) kW 1 1.2 1.6 2 2.5
Efficiency (normal mode)
25% Load 96.69 96.12 96.83 96.81 96.81
50% Load 96.80 96.91 96.82 96.85 96.84
75% Load 96.50 96.72 96.28 96.48 96.45
100% Load 95.92 96.42 95.83 95.92 95.81
Efficiency (ECO mode) Up to 98.9%
Max Flow M3/hr 1020 1530 1530 2040 2550
Table 12.8 Efficiency and loss
12 Specifications
187
Vertiv™ Liebert® EXM2 UPS User Manual