12 Specifications
This chapter lists the UPS specifications.
12.1 Conformance and Standards
The UPS has been designed to comply with the European and international standards listed in Table 12.1 below.
Item N orm ative refere nce
General safety requirements for UPS EN62040-1/IEC62040-1/AS62040-1
EMC requirements for UPS EN62040-2/IEC62040-2/AS62040-2 (Class C3)
Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
Environmental aspects - requirements and reporting EN62040-4/IEC62040-4/AS62040-4 (VFI SS 111)
Table 12.1 European and international standards
N O T E: T he product standards in this table incorporate relevant comp liance clauses with generic IEC
and E N standard s for safety (IEC /EN /AS60 9 50 ), electrom agnetic em issio n and im m unity
(IEC /E N/AS61000 series) and construction (IEC /EN /AS60 146 series and 60529).
12.2 Environmental Characteristics
Item Un it
Ra ted po wer (kV A)
100 /120 /150/160/200/25 0
Noise within 1m (in the front) dB (A) 68
Altitude m 1500; derate power by 1% per 100m between 1500m and 3000m
Relative humidity %RH 0 to 95%, non condensing
Operating temperature °C 0 to 50°C
Storage and transportation temperature for UPS °C Storage: -25°C ~ +55°C; transportation: -40°C ~ +70°C
Over-voltage level Level 2
Pollution level Level 2
Grid system TN, TT, IT
Table 12.2 Environm ental characteristics
12 Specifications
183
Vertiv™ Liebert® EXM2 UPS User Manual

Table of Contents

Related product manuals