EasyManua.ls Logo

Vertiv Liebert EXM2 - IS-Relay Card

Vertiv Liebert EXM2
204 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.2.10 IS-Relay Card
The appearance of the IS-Relay card is shown in Figure 9.10 below.
Figure 9.10 A ppearance of IS-R elay card
The UPS provides IS-Relay card for the user to use the dry contact signal to monitor the UPS.
The functions of the IS-Relay card are listed in Table 9.3 below.
Pin Func tion O peration
1 Common-Low Battery
2 Low Battery Closed if low battery point occurs
3 Low Battery Closed if battery is OK
4 Common-UPS Fault
5 UPS Fault Closed if UPS fault occurs
6 UPS Fault Closed if no UPS failure
7 Common-On Battery
8 On Battery Closed if On Battery power (Utility failure)
9 On Battery Closed if not On Battery power (Utility OK)
10 Signal Ground Future release
11 Signal Ground Future release
12 UPS Any-Mode Shutdown Future release
13 Summary Alarm Closed if no alarm conditions are present
14 Summary Alarm Closed if summary alarm occurs
15 Common-Summary Alarm
16 On UPS Closed if On UPS (inverter) power
17 On Bypass Closed if On Bypass
18 Common-On Bypass
Table 9 .3 Fun ctio n of UPS IS-Relay card
9 Options
165
Vertiv™ Liebert® EXM2 UPS User Manual

Table of Contents

Related product manuals