Term in al Designation
Signal N am e
M axim um
Voltage
M axim um
Curren t
W ire Rang e
M axim um
Length
Re m arks
Fro m To
J7_6 TMP_BATT_IN
+12 V Power 10 mA 16-22 AWG 30 m
Internal battery
temp (analog
signal)
J7_8 +12V_DRY +12 V Power
J7_14 ENV_DET
24 VDC 10 mA 16-22 AWG 30 m
Battery room
temperature
status; Provided
by Vertiv
(optionally)
J7_18 GND_DRY
J7_21 TEMP_ENV_DRY
24 VDC 10 mA 16-22 AWG 30 m
Ambient
temperature
detection
J7_23 GND_DRY
Table 4 .6 Description of dry contact port J7 (continued )
4 Electrical Installation
49
Vertiv™ Liebert® EXM2 UPS User Manual